Model 921A Combustible Gas Meter
Model 921A Combustible Gas Meter
Measure total combustible gases (TCG) in oil-filled transformer nitrogen gas blankets with this rugged, portable instrument.
Model 921A Manual
Download PDF(1 MB) »
Model 921A Data Sheet
Download PDF(101 kB) »
The Arbiter Systems®, Inc. Model 921A Combustible Gas Meter is a rugged, portable instrument that measures total combustible gases (TCG) in oil-filled transformer nitrogen gas blankets. TCG measurements have been shown to be good indicators of transformer health.
The supplied cylinders of Instrument Air, Zero Grade Nitrogen and 1 % Methane in Nitrogen calibration gases support field calibration, after which TCG measurements are virtually automatic.
The Model 921A also has a built-in gas pressure sensor. By connecting the gas sampling hose to the PSI port and pressing PSI, the blanket fill gas pressure can be accurately measured.
The Model 921A is provided with a hard-sided transit case, along with instrument air, nitrogen, and 1 % calibration gas cylinders and all necessary regulators and accessories.
Gas cylinder recycling suggestion: Typically the cylinders can be vented to the atmosphere, punctured, and then recycled as steel scrap. However, it is best to contact the local recycling facilities so specific laws/rules are not violated.
- Measures total combustible gases (TCG) in the field.
- Built-in gas pressure sensor.
- Includes regulators and accessories.
- Includes cylinders of Instrument Air, Zero Grade Nitrogen and 1 % Methane in Nitrogen calibration gases.
- All shipments containing gas cylinders ship from the factory via FedEx Ground ONLY. Reshipping this non-flammable calibration gas through common carrier requires hazardous materials certification because the cylinder pressure is greater than 40 psi.
Input
TCG
Inlet Pressure | 1 PSIG to 5 PSIG, nominal |
Damage Inlet | Vacuum to 30 PSIG |
Gas Inlet | Female Luer Fitting |
Pressure
Damage Limit | Vacuum to 30 PSIG |
Gas Inlet | Female Luer Fitting |
Air
Purity | Zero-Grade Instrument Air, 21.00 % Oxygen |
Inlet Pressure | 20 PSIG to 25 PSIG or use supplied regulator |
Air Inlet | Female Luer Fitting |
Measurements
TCG
Range | 0 % to 10.0 % |
Accuracy | ± (5 % of reading + 1 count) |
Resolution | 0.01 % TCG |
Calibration | 1 % Methane = 1 % TCG |
Sensitivity to Various Gases
(reading for 1 % gas in nitrogen, typical)
Methane | 1.00 |
Carbon Monoxide | 0.48 |
Hydrogen | 0.86 |
Acetylene | 1.9 to 2.0 Note: Interactions between the catalyst and acetylene cause the sensitivity to gradually increase during a sequence of acetylene measurements. This does not affect the sensitivity to other gases, and the effect is reversed on standing. |
Ethylene | 1.92 |
Ethane | 1.64 |
Air (100 %) | - 0.07 Note: The thermal conductivity of air, being slightly higher than that of nitrogen, will cause a negative reading by virtue of differences in thermal conductivity. While not optimized as a thermal-conductivity detector, this is an indication that transformer gas is not reaching the Model 921A. |
Pressure
Range | 0 PSIG to 15 PSIG |
Accuracy | 0.5 PSI |
Interface
Operator
Display | 16 character alpha-numeric supertwist LCD |
Power Requirements
Internal Battery
Type | Gelled-electrolyte lead-acid, 6 V / 4 AH |
Operation | 400 measurements on full charge |
Charging Time | 8 hours typical |
General
Physical
Instrument/Size | 130 mm x 230 mm x 65 mm (5.125 in x 9.125 in x 2.625 in) |
Transit Case | 400 mm H x 380 mm W x 240 mm D (16 in x 15 in x 9.5 in) |
Shipping | 533 mm x 533 mm x 533 mm (21 in x 21 in x 21 in), container |
Weight | 3 kg (7 lbs), net (instrument) |
Environmental
Temperature | Operating: 0 °C to + 50 °C |
Included | |
---|---|
AP0001800 | Wall-mount Power Supply: 120 Vac, 60 Hz; 12 Vdc, 0.8 A |
AP0002500 | Automobile lighter adapter |
AS0019100 | Calibration Gas Regulator |
AS0019300 | Transformer gas hose assembly |
AS0019402 | Calibration gas hose assembly (red) |
AS0019406 | Calibration gas hose assembly (blue) |
AS0019500 1 | Calibration Gas - Instrument Air |
AS0019600 1 | Calibration Gas - Zero Nitrogen |
AS0019700 1 | Calibration Gas - 1 % Methane in Nitrogen |
AS0096300 | Operation Manual (921) |
Available | |
AS0019501 1 | Calibration Gas - Instrument Air - Case of 12 |
AS0019601 1 | Calibration Gas - Zero Nitrogen - Case of 12 |
AS0019701 1 | Calibration Gas - 1 % Methane in Nitrogen - Case of 12 |
AS0020500 | Syringe Adapter (Kit of 5 each) |
AS0020800 | Bag of 10 Particulate Filters |
AS0026900 | Transformer Hose In-Line Filter Kit |
AS0026901 | Transformer Hose In-Line Filter Kit - Bag of Five |
AS0035100 | Annual Filter Maintenance Kit |
AS0061790 | Transit Case without Accessories (921A) |
BT0000700 | 6.0V Lead Acid 4.0Ah Sealed (921A) |
HP0018400 | Plug Luer Male w/ Locking Nut |
1 Ships from factory FedEx Ground ONLY. Reshipping this non-flammable calibration gas through common carrier requires hazardous materials certification because the container pressure is greater than 40 psi.
No additional software information is available for this product
Firmware Information (EPROM based firmware is not available for download) | |
---|---|
921_Firmware_24Oct2012 | Requires an EPROM update at Arbiter. Not field installable. |
Firmware Version and Related Information
EEPROM Update (921_Firmware)
Version | Rev Level | Version Notes |
---|---|---|
24Oct2012 |
|
TCG Measurement Comparison
Download model_921a_vs_mcgraw.pdf (14 kB) »
Model 921A combustible Gas Meter Filter Replacement Instructions
Download model_921a_filter_replacement_instructions.pdf (132 kB) »
Model 921A Sensor Change Update
Download 921a_sensor_change_update.pdf (27 kB) »
1 % Methane In Nitrogen (MSDS)
Download methane_in_nitrogen.pdf (233 kB) »
Zero Grade Nitrogen (MSDS)
Download nitrogen.pdf (30 kB) »
Instrument Air - Oxygen in Nitrogen Mixture (MSDS)
Download oxygen_in_nitrogen.pdf (107 kB) »